Carbon fiber fabric strengthening pull-out test

Normal carbon fiber fabric pull-out test tensile strength > 2.5 MPa, greater than this data is recognized as the carbon fiber fabric test qualified!

The carbon fiber fabric drawing test can be done on the 3 day after the carbon fiber sample is solidified. Generally, the experimental mold of the drawing instrument is bonded with adhesive, and the curing can be completed in 30 minutes, and the next step can be carried out.

Carbon fiber fabric strengthening pull-out test

Cutting and separating carbon fiber specimen edge and carbon fiber fabric by cutting machine.

carbon fiber

Install the drawing instrument and fix the base and the original structure wall.

Carbon fiber fabric strengthening pull-out test

After drawing, the concrete thickness of the broken ring interface is about 2~4mm, which basically shows that the experiment is qualified.

Carbon-fiber-fabric-strengthening-pull-out-test23.jpg

The failure of the original concrete section.

Carbon-fiber-fabric-strengthening-pull-out-test3.jpg

Normal carbon fiber fabric pull-out test tensile strength > 2.5 MPa, greater than this data is recognized as the carbon fiber fabric test qualified!


Horse Construction Recommended Products

You can find anything here you are in need of, have a trust trying on these products, you will find the big difference after that.

HM-20 Unidirectional Carbon Fiber Wrap

High strength, unidirectional carbon fiber wrap pre-saturated to form a carbon fiber reinforced polymer (CFRP) wrap used to strengthen structural concrete elements.

See more >

HM-180C3P Carbon Fiber Adhesive

Good impregnation carbon fiber adhesive for applying carbon fiber reinforced polymer(CFRP) wrap for structural strengthening

See more >

HM-1.2T Unidirectional Carbon Fiber Strip

High strength carbon fiber reinforced polymer (CFRP) strip / laminate / plate for structural strengthening and concrete repair

See more >

Back
Top
Close